How to Size a Battery Pack 2

-continued from "How to Size a Battery Pack - Part 1"  and see our latest updates: "Battery Bank Sizing: The Right Way! and "Full Storage System Sizing: The Right Way!"

To begin, you need to divide the average daily DC energy consumption by your system’s voltage; this will provide you with the average ampere-hours that your batteries would have to cover in a day.

[(AC Average Load/ Inverter Efficiency) + DC Average Load] / System Voltage = Average Daily Ampere-hours

[(720 Wh/ %90) + 160 Wh] / 12 V = 80 Ah

By multiplying the average daily ampere-hours by the number of days of autonomy, you’ll easily determine the necessary ampere hours that your system has to provide.

Average Daily Ampere-hours x Days of Autonomy = Total Ampere-hours

80 Ah x 5 days = 400 Ah

At this stage it is important to note that, it is not advisable to discharge your batteries below 50% of their capacity. The lower you discharge the batteries, the shorter your batteries will last for.

You have already determined the load capacity for your batteries. You should make a battery selection at this point to see how many batteries you will need in parallel.

Let’s pick the Surrette 6V, 400 Ah batteries 

Total Ampere-hours / (Discharge Limit x Selected Battery Capacity) = Batteries in parallel

400 Ah / (50% x 400 Ah) = 2 batteries in parallel

It is advised to round the number up if it’s not an integer (i.e. 2.12 would round up to 3; better than to be safe than sorry).

Calculating the number of batteries in series is easy. You basically divide the system voltage by the battery voltage. Let’s assume your system voltage is 24 Volts.

System Voltage / Selected Battery Voltage = Batteries in series

24 V / 12 V = 2 batteries in series

[image credit: mediaglobal]

Comments

Essa Radhyan commented 3 years 11 months ago

Regarding this formula ( [(AC Average Load/ Inverter Efficiency) + DC Average Load] / System Voltage = Average Daily Ampere-hours )
What do you mean by system voltage ? Is it the voltage number of solar array or battery bank?

Rayan commented 3 years 11 months ago

Regarding to your comment mr/ms. Essa Radhyan , the "system voltage" what he is saying was the voltage capacity of your selected battery you buy, because solar array commonly focus on (Watts/per panel) depending on your estimated total appliances load.

Marco Ekuru commented 2 years 4 months ago

Where is the 720 coming from

The 720 is just a random AC load for illustration.  Thanks again.